1. 風機答應全(quan)(quan)壓起動(dong)(dong)(dong)或(huo)降(jiang)壓起動(dong)(dong)(dong),但應留意(yi),全(quan)(quan)壓起動(dong)(dong)(dong)時的(de)電(dian)流(liu)約為5~7倍的(de)額(e)定電(dian)流(liu),降(jiang)壓起動(dong)(dong)(dong)轉(zhuan)距與電(dian)流(liu)平方(fang)成正(zheng)比,當(dang)電(dian)網容量不足時,應采用(yong)降(jiang)壓起動(dong)(dong)(dong)。(當(dang)功率大于11KW時,宜采用(yong)降(jiang)壓起動(dong)(dong)(dong)。)
2. 風(feng)機(ji)在試車時,應(ying)當(dang)真(zhen)閱讀產品仿單,檢(jian)查接(jie)線方(fang)法是(shi)否(fou)同接(jie)線圖(tu)相符;應(ying)當(dang)真(zhen)檢(jian)查供應(ying)風(feng)機(ji)電源(yuan)(yuan)的工作電壓是(shi)否(fou)符合要求,電源(yuan)(yuan)是(shi)否(fou)缺相或同相位,所配電器元件的容量是(shi)否(fou)符合要求。
3. 試車時人(ren)數不(bu)(bu)少于(yu)兩(liang)人(ren),一人(ren)控制電(dian)源,一人(ren)觀察風(feng)機運轉情況(kuang),發(fa)現(xian)異常現(xian)象(xiang)立刻(ke)(ke)停機檢查;首先檢查旋轉方(fang)向是(shi)否(fou)準(zhun)確;風(feng)機開(kai)(kai)始運轉后,應立刻(ke)(ke)檢查運轉電(dian)流是(shi)否(fou)平衡、電(dian)流是(shi)否(fou)超過額定(ding)電(dian)流;若(ruo)不(bu)(bu)有正常現(xian)象(xiang),應停機檢查。運轉五分鐘后,停機檢查風(feng)機是(shi)否(fou)有異常現(xian)象(xiang),確認無異常現(xian)象(xiang)再(zai)開(kai)(kai)機運轉。
4.雙速(su)風(feng)機(ji)(ji)試車(che)時,應先起動低速(su),并檢查旋轉方向(xiang)是否(fou)準確;起動高(gao)速(su)成時必(bi)需待風(feng)機(ji)(ji)靜止后再起動,以防高(gao)速(su)反向(xiang)旋轉,引起開(kai)關跳(tiao)閘及(ji)電機(ji)(ji)受損。
5.風機達到正(zheng)常(chang)轉速時,應檢測風機輸(shu)入(ru)電(dian)(dian)流(liu)是否正(zheng)常(chang),風機的運行電(dian)(dian)流(liu)不能超過其額定電(dian)(dian)流(liu)。若運行電(dian)(dian)流(liu)超過其額定電(dian)(dian)流(liu),應檢查供應風機的電(dian)(dian)壓是否正(zheng)常(chang)。
6.風機所(suo)需電機(ji)(ji)功率是(shi)指在一定工況下,對離心風(feng)(feng)機(ji)(ji)和(he)風(feng)(feng)機(ji)(ji)箱,進(jin)(jin)風(feng)(feng)口全(quan)開時(shi)所(suo)需功率較大。若進(jin)(jin)風(feng)(feng)口全(quan)開進(jin)(jin)行運轉,則電機(ji)(ji)有損(sun)壞的(de)可(ke)能。風(feng)(feng)機(ji)(ji)試(shi)車(che)時(shi)最好將風(feng)(feng)機(ji)(ji)入(ru)口或出口管(guan)路(lu)上(shang)的(de)閥(fa)門(men)封(feng)閉,運轉后將閥(fa)門(men)徐(xu)徐(xu)開啟,達到所(suo)需工況為止,并留意風(feng)(feng)機(ji)(ji)的(de)運轉電流是(shi)否超過額定電流。